GradeShift & GradeShift UDL
GradeShift UDL (DC6) offers a single piece of hardware for every grade of risk with interchangeable EN Grades. You simply pick the grade required and can remotely change the grade at any time if required.


Quick Guide
Step 1 - Site Survey
Use a CSL Signal Analyser to determine if sufficient base stations are available at the site and that they can supply sufficient signal strength. This will determine the optimum location for the DualCom’s aerial to be mounted.
SITING THE AERIAL DO… • INSTALL VERTICALLY IN AN OPEN SPACE.
DON’T… • INSTALL CLOSE TO METAL OR SOURCES OF INTERFERENCE, I.E. WIRING, |
Step 2 - Installation
a – Ensure the aerial is mounted and connected in the correct position to achieve maximum signal strength. Apply power and wait for 5-8 minutes for the unit to connect to the network and download its programming file. Once completed the Green Signal Strength LED should be on or flashing, indicating an acceptable signal, the Red Fault LED should be off and the Blue Ready LED will be on. A percentage will also be shown on the SSD (Seven Segment Display) which should be 40% or higher. Now the GradeShift can be located into a suitable enclosure for the grade of installation.
b – Wire the input triggers, attach the RS232/485 cable or connect the Control Panel’s Digi-Modem PSTN terminals to the GradeShift’s Dial Capture terminals (refer to wiring diagrams in Section 2 of this document). For a dual path device remember to connect for PSTN or LAN.
c – Connect the fault output terminals to the Control Panel as required (refer to wiring diagrams in Step 6 of this document).
d – Power down the the Power Supply Unit (PSU), connect 9-30volts DC supply to the GradeShift’s power terminals and repower the PSU. Note that any voltage below 12v will indicate a low battery warning.
e – For installations using Dial Capture no GradeShift configuration is required. Simply check that your Digi-Modem has an ARC telephone number (ie 01) and an account number (ie 1234), select your signalling format, connect the GradeShift and test.
f – For pin triggering installations, ensure that the panel is in its normal state then press and hold the TEST/LEARN button for 3 seconds until the Green Signal Strength LED and the Yellow Communications LED flash alternately. Please note it is recommended that this step is not carried out until the instructions above have been completed.
IF USING A SEPARATE PSU TO POWER THE GRADESHIFT, MAKE SURE THE 0V IS COMMON BETWEEN THE PSU AND THE CONTROL PANEL. |
Step 3 - Test & Self Learn
To send test signals, tap the TEST/LEARN button (less than 1 second). The 7 SSD should change to c1, c2, c3, A. (A = the Gemini Platform acknowledges the alarm signal). Simultaneously, the Yellow Communications LED indicates comms progress. If available, GradeShift will test the secondary (wired) path using C1, C2, C3, A to indicate successful communication.
If the test is not successful the Red Fault LED will light for 2-3 seconds at the end of the sequence. The GradeShift will make multiple call attempts if unsuccessful.
To self-learn the inputs, push the TEST/LEARN button for 3-5 seconds. ‘Pi’ will be displayed during the self-learn process.
Step 4 - Check Signals
Once you have successfully tested your GradeShift, make sure that you check with your ARC to see that they are receiving signals. This can be achieved by calling your ARC or using their web-based secure platform.
IF YOU HAVE PURCHASED A DUAL PATH DEVICE YOU MUST ENSURE BOTH PATHS ARE CONNECTED BEFORE LEAVING SITE. |
Step 5 - Advanced Instructions
LINE FAULT
Ensure you wire the fault output in accordance with the standard you wish to adhere to.
FAIL TO COMMUNICATE MONITORING USING DIAL CAPTURE
If you want to monitor the Dial Capture connection, connect an output configured as PSTN line fault on your Control Panel to one of GradeShift’s inputs. Designate that input as Dial Capture fail at your ARC. For wiring instructions see step 6
RS232/485 – for installations using RS232 or RS485 simply follow the wiring diagrams in step 6.
LAN – For installations using LAN as a communication path connect a Cat5 (or higher).
GRADESHIFT WILL AUTOMATICALLY LEARN WHETHER THE PSTN LINE REQUIRES A 9 TO DIAL OUT AND WILL SAVE THE SEQUENCE TO ITS CONFIGURATION. IF THE PSTN CHANGES AND NO LONGER REQUIRES A 9 TO DIAL OUT GRADESHIFT WILL REVERT THE CHANGES. |
Step 6 - Wiring
PIN TRIGGERING
In the operation, GradeShift is triggered by applying or removing zero volts to the input terminals 1-12. No external pull-up resistors will be required. This is generally achieved via the digital communicator outputs of an intruder alarm or similar Control Panel. GradeShift will signal alarm conditions and will generate the relevant messages and forward them via Gemini to the ARC. Installers are advised that the intended use should avoid situations where the rate of triggering exceeds the rate at which messages may be sent to, or received by, the ARC receiver.
DIAL CAPTURE
In this operation, GradeShift simulates and replaces the phone line connection to the Control Panel’s Digi-Modem.
The Control Panel’s Digi-Modem must use one of the following alarm formats: Fast Format, Contact ID or SIA. In the event the Control Panel needs to send a signal to the ARC, GradeShift will capture the message and forward it, via Gemini, to the ARC. The Digi-Modem must have an ARC telephone number (ie 01) and account number (ie 1234) programmed for Dial Capture to work.
If you want to monitor the Dial Capture connection, you will need to connect an output configured as a PSTN line fault on your Control Panel to one of GradeShift’s inputs. That input then needs to be designated as Dial Capture Fail at your ARC.
PSTN
RS232/485
For further instructions on Control Panel programming please review the how to guides on the Installer Zone
Troubleshooting
Q – The Red Fault LED is continuously flashing, what does this mean?
A. This happens when the unit is first powered and needs to download its configuration file from the Gemini Platform which can take 5-8 minutes. You must ensure that the Yellow Service (SVC) LED is flashing every 3-5 seconds, which indicates that the unit is connected to the mobile network.
Q – The GradeShift repeats the ‘power-up’ sequence but never completes it.
A. The power supply has a low output voltage or is unable to supply the current required by the GradeShift when it is activated. Check the power supply with a multimeter. Also, test the GradeShift’s operation when powered by a ‘known good’ 12-volt battery.
Q -The Red Fault LED is on, what is the problem?
A. Please refer to the error code on the SSD and the error code list at the end of this document.
Q -Triggering via ‘Dial Capture’ does not seem to work.
A. During communication between the Control Panel and the GradeShift, the display should show ‘DC’. If ‘DC’ is displayed, but c1, c2, c3, A is not, the panel may not be compatible or is configured to send a protocol that GradeShift does not recognise. If available, check the Control Panel’s programming and select an alternate signalling format. Please check our online compatibility table for the latest list of compatible Control Panels and formats: www.csl-group.com.
Q – The ARC is not receiving messages.
A. In most cases the GradeShift will explain the reason a signal cannot be sent to your ARC using an error code shown on the SSD. If, after trying to rectify the displayed fault, the GradeShift can still not transmit to your ARC please contact CSL Technical Support.
ERROR CODES
ERROR CODE (E+) | DESCRIPTION | WHAT YOU SHOULD DO |
0 | No Errors | N/A |
l o | Low supply voltage | Check supply voltage |
1 | NVM missing or not fitted correctly | Check NVM fitted correctly |
2 | NVM data error. Not programmed correctly | Check NVM programming. Call CSL Technical Support |
3 | NVM checksum fault | Check NVM programming. Call CSL Technical Support |
4 | Power Fault. Voltage low etc. | Check supply voltage is in the 10 – 30 volt range at all times |
5 | 485 Bus Port enabled but comms have failed | Check the 485 Bus Port connections to the Control Panel or the Plug-on Adapter |
10 | Radio. No base stations detected | Check aerial connection and base station signals |
11 | Radio. Not registered on any GPRS network | Check SIM card and base station signals. Call CSL Technical Support |
12 | Radio. No response from radio module | Check module is fitted correctly. Check power. Call CSL Technical Support |
13 | SIM card missing or not fitted correctly | Check SIM card is fitted correctly |
14 | SIM card locked/disabled. No radio path operation possible | PUK Code required to unlock SIM. Call CSL Technical Support |
15 | SIM card PIN number is wrong | Check SIM PIN number in NVM. Call CSL Technical Support |
17 | Radio module faulty | Power down. Wait 1 minute. Re-power & re-check. Call CSL Technical Support |
18 | Radio. Interference or jamming signals detected | Check local radio environment. Use a CSL Signal Analyser |
21 | PSTN line DC voltage = low or none | Check PSTN connections to A&B terminals |
22 | PSTN. A phone, fax, etc. on the same line is off hook | Check for another phone, fax, etc. on the same line as DualCom or disable detection in the NVM |
23 | PSTN. Incoming ringing detected | Disable incoming ringing with Telephone supplier or disable detection in the NVM |
24 | PSTN dialling attempt. No dial tone | Check PSTN connections and that the service is available |
25 | PSTN. All call attempts have failed | Check PSTN connections and that the service is available |
31 | PSTN. Three successive call attempts have failed | Check SIM card fitted correctly. Check GPRS service |
32 | Radio / GPRS fault | Check SIM card fitted correctly. Check GPRS service. Check NVM programming |
41 | Radio / GRPS communications failure | Check Ethernet Cable is connected to LAN (IP) card. Check LAN cable is correctly connected to LAN Router/Hub/Switch at other end |
43 | LAN Ethernet Cable (e.g. Cat5) not connected | Check LAN wiring, Router, power supplies and DualCom’s IP programming. Call CSL Technical Support |
44 | No response from the Default gateway. (the Router to the Internet) | Check DualCom’s IP programming. Check Router is not firewalled. Call CSL Technical Support |
45 | LAN communications failed | Check DualCom’s IP programming. Check Router is not firewalled. Check Gemini Secondary Polling Server. Call CSL Technical Support |
47 | Invalid Router, Gateway or WAN address | Check DualCom’s IP programming |
51 | Radio path. All call attempts have failed. | Check all Radio settings in the NVM. Call CSL Technical Support |
99 | NVM data error. Not programmed correctly | Check NVM programming. Call CSL Technical Support |
CRITICAL ERRORS
To alert the User and Installer to critical error conditions, after the normal sounder beeps have timed out the GradeShift unit will continue to beep once every 5 minutes.
Fire Guide
MOUNTING
This device should be mounted inside the Fire Alarm Panel or inside a separate powered housing using, the sticky mounting pads supplied. Enclosure requirements for the GradeShift UDL Fire are the same as for the Fire Alarm Panel itself. The enclosure must provide the facility to indicate the state of the fault and acknowledge outputs on the device. For Fire Alarm Panels, the enclosure must meet the requirements of EN54-21 7.3 (e.g. IP30 or above) and the supplied sticker should be applied to the outside of the housing.
SECONDARY (WIRED PATH) CONNECTION OPTIONS
The PSTN connection requires an analogue telephone line. Connecting other telecoms equipment in parallel to the analogue telephone line used by this device can stop the unit sending polling calls and alarm calls to an Alarm Receiving Centre. Parallel connection should never be used for this device when it is used in a Fire system application. The PSTN line should be supplied as ‘outgoing calls only’, i.e. incoming ringing barred. The PSTN line should also be ex-directory and connected to this device only. Other equipment can be connected to the A1 & B1 terminals (i.e. series connection) to make outgoing calls only. Modifications to the telephone or data provision (including changes to the local IT network when a LAN connection is used) might prevent or hinder the transmission of alarm information. Additionally, this could cause false alerts which might cause customer inconvenience and/or (where it is provided) result in withdrawal of emergency service response.
GRADESHIFT UDL FIRE IS SENT OUT IN EN54-21 TYPE 2 CONFIGURATION (GPRS/PSTN). THIS IS NOT CONFIGURABLE BY THE INSTALLER |
The interface to the Fire Control Equipment should be via inputs (pins) and relay outputs, as described below. The DualCom’s ‘Dial Capture’ interface that emulates a PSTN line shall not be used, as it does not provide adequate status signalling back to the control equipment.
• AUX Relay Output: used for transmitting fire alarm ACK signals to the CIE.
• Normally Closed (N/C) Fault Relay Output: used for transmitting fault warning signals to the CIE. This relay will remain open during normal operation.
• Input 11: used for receiving the Fire Alarm/Restore signal from the CIE.
• Input 12: used for receiving Fault/Restore signal from the CIE.
• Input 1-10: used for receiving PIN inputs from any other device (i.e. security CIE). PINs 1-10 take a lower priority than 11-12 when signalling.
The alarm codes generated by these inputs are as follows:
SIA | CONTACT ID | FAST FORMAT |
Pin 11: FA8011/FH8011 | Pin 11: Event 110 group 0 zone 11 | Pin 11 Channel 11 |
Pin 11: FA8011/FH8011 | Pin 12: Event 373 group 0 zone 12 | Pin 12 Channel 12 |
As default, inputs 11 and 12 are configured as digital inputs. They can be set up as End of Line (EOL) detection, Fully Supervised Loop (FSL) or digital inputs.
For FSL mode, a 10K and 2K2 end of line resistors should be fitted for detection of open circuit and short circuit. For EOL mode, a 10K end of line resistor should be fitted for detection of open circuit:
Inputs 11 and 12 can be configured for either EOL and FSL using the programmer menu:
• A button 4 times to P
• B button 3 times to Pi
• A button 5 times to PF
• B button 3 times to Fd
Use B button to scroll:
• Fd = DIGITAL
• FE = EOL
• FF = FSL
Press A button to select mode.
PINS 1 – 10 CAN BE TRIGGERED BUT THEY WILL NOT SEND FIRE ALARM/FAULT SIGNALS. |
For FSL or EOL, were the negative supply (0V) to the panel relay common and the panel N/C terminal to the DualCom input pin with the 10K resistor in parallel.
For Digital, wire the negative supply to the panel relay common and the panel N/O terminal to the DualCom input.
FAULT REPORTING & DUAL PATH OPERATION
To meet the EN54-21 requirements for monitoring on Type 1 and Type 2 Fire systems this device sends regular polling calls to the Gemini Network on all connected and active transmission paths. The Installer shall ensure that a reporting action has been agreed with the ARC for all alarm codes, transmission path failure notifications and Polling failure reports from the Gemini Platform.
GRADESHIFT UDL FIRE HAS BEEN DESIGNED TO WORK AS A DUAL PATH SIGNALLING DEVICE, INSTALLATIONS THAT USE ONLY 1 SIGNALLING PATH WILL NOT MEET THE SPECIFIED DP2 FAULT REPORTING TIMES. |
RELAYS
The Acknowledgment and Fault signals are triggered by the AUX Relay and Fault Relay respectively. Depending on how the CIE input works (active high or active low), please wire them as follows:
FAULT RELAYS
The fault relay labelled NC must be used. The device will ensure this remains open in a No Fault condition and it will close when any of the following conditions are met:
1 – The power is removed.
2– There is a short circuit in any of the interconnections between the CIE and the device. (FSL configuration only)
3 – There is an open circuit in any of the interconnections between the CIE and the device.
(For FSL and EOL configuration)
4 – An acknowledgement has not been received from the Gemini Platform within the allotted time after a Fire Alarm has been sent within 240 seconds (type 2), 100 seconds (Type 1)
5 – There are no transmission paths available. Please note, all available paths must fail before a fault warning is given.
6 -There is a watchdog event (program monitoring).
7 – There is a memory (CRC) monitoring fault.
A FIRE ALARM WILL NOT RESTORE UNTIL ALL FAULTS (WIRING OR PANEL) ARE CLEARED FAULT RELAY SHOULD BE WIRED TO THE FIRE PANEL FAULT INPUT OR TO A SEPARATE LIGHT EMITTING INDICATOR AS REQUIRED BY EN54-21 5.3.B |
The acknowledgement relay (ACK) is normally open. It closes when an acknowledgement of a Fire Alarm is received from the Gemini Platform. It is opened again when an acknowledgment of the Fire Alarm Restore signal is received from the Gemini Platform.
THE ACK RELAY WILL CLOSE EVEN IF AN ACKNOWLEDGMENT IS RECEIVED AFTER THE ALLOTTED TIME OF 240 SECONDS (TYPE 2) HAS EXPIRED, AS IN POINT 4 ABOVE. |
ACKNOWLEDGEMENT RELAY (ACK)
The acknowledgement relay should be used to indicate the successful receipt of a Gemini Platform acknowledgement either at the Fire Alarm Panel or by a separate light emitting indicator, as required by EN54-21 5.3.a
Technical Specs
Technical Specifications
Dimensions | 21 mm (h), 132mm (w), 94mm (d) | ||||||||||||
Weight | 140g including NVM and SIM | ||||||||||||
Temperature | -20C to +60C transit, -10C to +50C operating | ||||||||||||
Humidity | 0 – 80% non-condensing | ||||||||||||
Mounting | Any orientation | ||||||||||||
Warranty | 5 years | ||||||||||||
Power Requirement | 9.0v – 30.0v | ||||||||||||
Current Consumption | Quiescent = 20 mA Signalling = 200 mA | ||||||||||||
LED Indications |
| ||||||||||||
Radio Path | 2G GSM and 3G GPRS services | ||||||||||||
Aerial | 50 ohm (nominal) on MMCX socket | ||||||||||||
Operation Method | Store and Forward (SIA) Pass Through (Fast Format/CID) | ||||||||||||
CIE Interconnections | Input ‘pin triggering’ (Parallel) 12 channels, Analogue (Dial Capture), RS232 Serial, RS485 Bus | ||||||||||||
RCT Protocols | Fast Format/Contact ID/SIA | ||||||||||||
Input Terminals | Max +30v, Min 0 Vdc (reference supply 0v terminal) 100k pull-up resistor to +5v | ||||||||||||
Low Battery | 9.8v falling, 12.0v recovery | ||||||||||||
Fault Output | Changeover contacts (60v max, 100mA max) | ||||||||||||
Aux Output | Normally Open contact, may be inverted (60v max, 100mA max) | ||||||||||||
General Purpose outputs | Four. Each switched to 0v (30v max, 100mA) | ||||||||||||
User Serviceable Parts | There are no user serviceable parts within the GradeShift | ||||||||||||
Standards | Suitable for use in alarm systems complying to: EN50136-1:1998 Security Grade 4/DP3 EN50136-2:2012 SP3 (RADIO) SSF 114 v2 Larmklass 2 EN50131-10 Type Y ATS Classification: EN50136 ATS5/SP3 ATS 5 parameters: D3/M3/T4/S2/I3/A3 | ||||||||||||
Environmental | EN50136/EN50131 Environmental class II Device should not come into contact with water | ||||||||||||
Emissions | EN55022 | ||||||||||||
Installation | The CS5301-01 shall be installed by a service person and be powered by a Limited Power Source in accordance with clause 2.5 of EN 60950-1 or equivalent, not exceeding the maximum voltage of 30 Vdc, capable of delivering a minimum current of 200mA and be current limited (fused) to 1A. It shall be installed inside an enclosure of another I&HAS component which shall be that of a CIE conforming to EN 50131-3, or a PSU conforming to EN 50131-6. |
Figure 2 – LED Indications
LED LABEL | DESCRIPTION | LED STATUS | |||
ON | FLASHING | OFF | OTHER | ||
Green | GPRS Signal Strength | Strong Signal Strength | Acceptable Signal Strength | Low Signal Strength, not acceptable | LED off and Red Fault LED on indicates no signal |
Yellow | Communications | Input is triggered or Dial Capture is in progress | Sending a message to Gemini and ARC | No communication is in progress | Rapidly flashes to show successful communication |
Red | Fault | Fault present see troubleshooting section | NVM contains factory defaults | No faults exist | On for 2 seconds indicates communication failure |
Blue | Ready | Unit is ready to send messages to Gemini and ARC | N/A | Unit is busy and not ready to send new messages | LED off and Red Fault LED on indicates programming file is yet to be downloaded (usually takes 5-8 mins from power up with good signal) |
Service (SVC) (next to aerial socket) | Network Status | N/A | SIM card registered on network | There is insufficient power or no power connected to the DualCom | Rapid flashing indicates unit is not registered to network |
FAQs
Why is a Broadband Filter necessary?
When ADSL (Broadband) digital data is supplied on a normal PSTN telephone line then an ADSL (Broadband) Filter must be fitted between that telephone line and each item of ‘non-digital equipment because:
1 – The operation of ‘non-digital equipment may be disrupted or completely inhibited if ADSL (Broadband) digital data is allowed into it from the telephone line.
2 – The operation of the ADSL (Broadband) equipment may be disrupted or completely inhibited by the connection of unfiltered ‘non-digital equipment to the telephone line. ‘Non-digital’ equipment means anything that can be used on a normal analogue PSTN telephone line, e.g. a Phone, Fax, DualCom, Control Panel Digi-Modem.
What if there appears to be random triggering of the DualCom?
In the event you are using two separate power supplies, one for the alarm panel and the other for the DualCom – ensure there is a common 0v across both power supplies. I.E. Wire the 0v of one power supply to the other power supply’s 0v.
Ensuring both the alarm panel and the DualCom have a common negative (0v) supplied will prevent any unexpected behaviours, including random triggers.
What if the Telephone path signal is not received by the Alarm Receiving Centre?
Use the A & B Buttons to check that the PSTN path is active. (See page 6 in the Quick Guide)
Check that the PSTN line is properly connected. Check with a multi-meter that approximately 50 volts DC is present across the PSTN terminals marked A and B. Check that when the PSTN path is triggered on the DualCom, the voltage across the telephone line A and B terminals drops to between 6v and 14v DC.
Connect a telephone to the PSTN line and make a call to ensure that it is fully functional. If you can make outgoing calls on the PSTN line, then try the receiver number programmed within the DualCom. You can get this number by calling the CSL Technical Support team on +44 1895 474 444. If your call goes through to the receiver number, you should hear a fax tone.
Disconnect any other equipment that is using the same PSTN line to ensure that it is not inhibiting the DualCom. Where ADSL (Broadband) digital signals are on the telephone line ensure that an ADSL (Broadband) filter is fitted between the DualCom and the PSTN line.
For further support, please contact the CSL Technical Support team on +44 1895 474 444. Alternatively, you can email support@csl-group.com.
What if the Radio path signal has not been received by the Alarm Receiving Centre?
Check using the 7-segment display that the radio signal strength is sufficient (40 or greater) and that the signal strength on the display is not flashing on and off. If the signal strength is flashing on and off on the display, then please contact CSL Technical Support for assistance.
Check with a multi-meter that the voltage supply to the DualCom is correct and does not dip when the DualCom is signalling. The DualCom requires voltage between 9v – 30v. If the voltage supply is good, then please check the mA supply – the DualCom will draw 20 mA if idle and 200mA when signalling. If inadequate mA is being supplied to the DualCom during either state, then this would indicate an issue with the power supply.
For further support, please contact the CSL Technical Support team on +44 1895 474 444. Alternatively, you can email support@csl-group.com.
What if the Wired LAN (IP) signal has not been received by the Alarm Receiving Centre?
Check, using the LEDs that no LAN path faults exist.
Check that the LAN has a route to the Internet. Ensure that Firewalls, Routers etc will allow external access. Refer to IT staff on site.
Check that the LAN has a DHCP Server function. The LAN card requires this when first connected to the LAN. Refer to IT staff on site. Check with a meter that the voltage supply to the DualCom is correct and does not dip when the DualCom is signalling.
Is the GradeShift UDL dual-path capable?
Yes. The GradeShift UDL supports a secondary path in addition to the primary GSM path. The following Gradeshift UDL variants are available:
- GradeShift UDL GSM only.
- GradeShift UDL GSM + LAN.
- GradeShift UDL GSM + PSTN (discontinued due to All IP & the Copper Switch-Off).
Important Note: The GradeShift UDL only supports one secondary path at a time. I.e. It cannot support GSM + LAN + PSTN. It can only support GSM + LAN or GSM + PSTN.
Which path is the primary signalling path?
The GSM path will always be the primary signalling path. The LAN or PSTN path will always be the secondary path. If the GSM path fails to signal, the LAN or the PSTN path will take over.
Important Note: The GradeShift UDL only supports one secondary path at a time. I.e. It cannot support GSM + LAN + PSTN. It can only support GSM + LAN or GSM + PSTN.
How can I tell if all the signalling paths are working?
Every time the GradeShift UDL signals, it will display a series of characters on the segment display to show the signalling steps. The best way to test if the paths are working is to get the GradeShift UDL to send a test signal on all working paths.
To send a test signal on all working paths, simply tap the small play button on the front of the unit.
- Poll signals will show a small c1, c2, c3 and then a flashing A. The characters will be on the upper segment of the display.
- GSM signals will show a small c1, c2, c3 and then a flashing A. The characters will be on the lower segment of the display.
- LAN or PSTN signals will show a large C1, C2, C3 and flashing A. The characters will take up both the upper and lower segments, making the secondary path signalling easy to distinguish from the GSM.
Important Note: During signalling, if the segment display does not progress all the way through the steps, this would mean the signalling path has failed to signal out. E.g. If the segment display shows a small c1, but does not progress to c2, c3 then a flashing A, this would mean there was an issue with the GSM path’s ability to signal out.
How does the GradeShift UDL interface with my panel?
The GradeShift UDL supports 3 connection methods, and each connection method supports 3 signalling protocols.
Connection methods:
- Hardwired Pins
- Dial Capture (Connects to the panel Digi Modem)
- Serial RS-485 (Connects to Honeywell and Orisec panel data lines)
Signalling protocols:
- Fast Format
- Contact ID
- SIA
If you prefer to call or email us, you can reach our Technical Support team on +44 1895 474 444 and support@csl-group.com.
Does the LAN path support DHCP?
Yes, by default the LAN path is set to use DHCP. This means the GradeShift UDL will automatically try to get the network configuration when it is connected.
The LAN path can be changed from DHCP to Static IP if the network on a site requires it. Please note if the LAN path needs changing to static IP, we will require the following details:
- Static IP Address
- Subnet Mask Address
- Default Gateway Address
- Primary DNS Address (optional)
- Secondary DNS Address (optional)
This information should be provided by the company that is managing the IT network for that site.
Important Note: This change can only made by our Technical Support team. Please get in touch by calling +44 1895 474 444 or email support@csl-group.com.
Can the LAN path be changed to Static IP?
Yes, the LAN path can be changed from DHCP to Static IP and vice versa. Please note if the LAN path needs changing to static IP, we will require the following details:
- Static IP Address
- Subnet Mask Address
- Default Gateway Address
- Primary DNS Address (optional)
- Secondary DNS Address (optional)
This information should be provided by the company that is managing the IT network for that site.
Important Note: This change can only made by our Technical Support team. Please get in touch by calling +44 1895 474 444 or email support@csl-group.com.
Does the GradeShift UDL need ports opened to work on LAN?
Yes. Please ensure that these port numbers are not blocked by settings within routers/firewalls.
Port Type: TCP
Port Numbers:
443
8580 – 8600
8620
8999
9050 – 9051
9600 – 9619
9900
10443
20001 – 20002
Other useful information:
- The LAN module on the GradeShift UDL supports 10mbps half-duplex only.
- Destination IP Addresses, Subnets and Ranges:
Subnet: 185.201.164.0/22
Range: 87.84.219.34-87.84.219.46
Range: 87.86.241.82-87.86.241.94
Host: 87.86.190.253 - The signals that will be transmitted from the DualCom when polling and alarming are 750 bytes each. Usage per month does not exceed 35 Megabytes.
What are the Destination IP addresses for the LAN path?
Here are the addresses the GradeShift UDL will communicate to when signalling on the LAN path. The network administrator may require these details to allow the signals through their firewall.
Destination IP Addresses, Subnets and Ranges:
- Subnet: 185.201.164.0/22
- Range: 87.84.219.34-87.84.219.46
- Range: 87.86.241.82-87.86.241.94
- Host: 87.86.190.253
Other useful information:
- Please ensure that these port numbers are not blocked by settings within routers/firewalls.
Port Type: TCP
Port Numbers:
443
8580 – 8600
8620
8999
9050 – 9051
9600 – 9619
9900
10443
20001 – 20002
- The LAN module on the GradeShift UDL supports 10mbps half-duplex only.
- The signals that will be transmitted when polling and alarming are 750 bytes each. Usage per month does not exceed 35 Megabytes.
What is the best way to test path fails to the ARC?
Enter engineer mode on the GradeShift UDL to lower path fail times. Then disconnect the path you want to force into fail.
To enter engineer mode:
Press A until “t” then press B twice. Engineer mode will last for 10 minutes then exits out automatically, returning the path fail times back to normal.
What polarity do I need to use to trigger the pins on the GradeShift UDL?
By default, the pins are configured for “Negative Applied”. For best results, please run a self-learn on the pins once you have wired in all the pins you need.
To run a self-learn:
Press and hold the small play button on the front of the unit until the letters “Pi” are displayed on the screen, then let go.
The pin learn will detect all the pin wirings and match the pin config to your panel’s outputs.
E.g. If your intruder alarm that wires into pin 3 is set for “Negative Removed”, the self-learn will invert pin 3 on the GradeShift UDL and change it from “Negative Applied” to “Negative Removed” to match your intruder alarm.
Important Note: The GradeShift UDL pins only support Negative voltage. Positive cannot be used.