Aritech Advisor Advanced – Dial Capture

Panel Connection – Dial Capture

Manufacturer

Carrier

Model

Aritech ATS Advanced

Cable required?

MCM connected to:

  • DualCom Pro 1 – MCM plug-on module CS.1.402
  • DualCom Pro 2 – DI & AL

Panel Profile

ARITECH-ADVANCED-MCM

Panel Bus Connection

Dial Capture

Technical Notes

To enter engineer mode, access must be allowed via a setting in User mode. After defaulting the panel, the panel will ask questions on power up.

User Code : Menu 8:2:1 – Need Acc [YES]

Eng Code : Menu 8: Sys Opt > 7: Panel & AB Opts > 9: Remote Config – YES

Panel Connection Information

DualCom Pro 1 – MCM plug-on module – Line A
DualCom Pro 2 – DI

PSTN A

DualCom Pro 1 – MCM plug-on module – Line B
DualCom Pro 2 – AL

PSTN B

Panel Programming

  • Enter : Installer Mode (Engineer)
  • Select: 9>Dialler menu
  • Enter: 1> CS
  • Enter: 01> CS 1
  • Set: CS name [CS 1]
  • Enter: 2>‘Transm Path’ [PSTN]
  • Enter 3>‘Protocol’
  • Set: (X)SIA’
  • Enter 4>Phone [01234567890]
  • Enter 5>‘Accounts’ menu
  • Select: ‘Area ‘1’ with [account numbers]
  • Select: ‘Area ‘2’ with [account numbers OR blank]
  • Select: ‘Area ‘3’ with [account numbers OR blank]
  • Select: ‘Area ‘4’ with [account numbers OR blank]
  • Enter 6>‘Mode’
  • Set: Primary CS’
  • Enter 7> retry count [10]
  • Enter 8>‘Protocol opt’
  • Set: ‘(X)SIA’
  • Set ‘Area Modifier’ to ‘[ON]’
  • Set ‘Name Chars’ to ‘[30]’
  • Set ‘Event Number’ to ‘[3 digits]’
  • Set ‘Subev codeing’ to ‘[Decimal]’
  • Set ‘SIA Frequency’ to ‘[Bell]’
  • Go back to ‘Dialler’ menu level
  • Enter 3>‘Path Options’
  • Enter 1>‘PSTN’
  • Enter 2>‘Line Fault’ menu and select option ‘[No]’
  • Go back to ‘Path Options’ menu level.
  • Enter 4>IP (If present)
  • Enter ‘Line Fault’ menu and select option ‘[No]’
  • Enter 4>‘PC Conn’ menu
  • Select 1>‘PC Conn 1’
  • Set 2>‘Trans Path’ to ‘PSTN’
  • Set 3>‘Modem Protocol’ to ‘V22’
  • Set 4>‘Phone Number’ to ‘None’ or blank
  • Set 5>‘Retry Timeout’ to ‘3’
  • Set 2>‘PC Callback’ to ‘Off’
  • Set 3>‘Encrypt Key 1’ as required
  • Set 4>‘Encrypt Key 2’ as required
  • Set 5>‘Listening Port’ to ‘n/a or None’
  • Set 6>‘Panel ID’ to ‘None’
  • Enter ‘Path Options’ menu
  • Enter ‘PSTN’
  • Set ‘Name’ to ‘PSTN’
  • Set ‘Line Fault’ as required
  • Set ‘Line Fault Delay’ to ‘0’
  • Set ‘Transmission Path’ to ‘PSTN’
  • Set ‘Dial Tone’ to ‘UK’
  • Set ‘Dialling’ to ‘DTMF’
  • Set ‘Ring Count’ to ‘1’
  • Set ‘Encryption’ to ‘No’
  • Exit Installer / Engineer Mode
  • Note: This may require a full panel and DualCom Pro reboot.