Kentec Syncro and Solo Series – RS232
Panel Connection – RS232
|
Manufacturer |
Kentec |
|
Model |
Syncro and Solo series |
|
Cable required? |
A dual row, 10-way terminal housing with 2.54mm pitch with pins 1, 5 and 7 wired. |
|
Panel Profile |
KENTEC-FIRE-RS232 |
|
Panel Connection |
RS232 |
|
Technical Notes |
The panel profile defaults to EN54 Fire Mode. Please contact Tech Support if you require to configure the panel in non-Fire mode. If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
DualCom Pro to Panel Wiring

Panel Connection Information
|
RS232-T |
Pin 1 |
|
RS232-R |
Pin 7 |
|
RTN |
Pin 5 |
Panel Setup
The SPT expects the panel address to be 1. This can be viewed using the panel manufacturer’s software and ensuring the node address is set to 1 in the Configure Node window.