Honeywell Notifier – RS232
Panel Connection – RS232
|
Manufacturer |
Honeywell |
|
Model |
Notifier |
|
Version |
ID2000 |
|
Cable Required? |
Unterminated serial cable with 9 Way D-Type IDC socket. |
|
Panel Profile |
NOTIFIER-PRINTER-RS232 |
|
Panel Connection |
RS232 |
|
Technical Notes |
ID3000 is not supported. If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
Panel Connection Information
|
RS232-T |
9 Way D-Type Pin 2 |
|
RS232-R |
9 Way D-Type Pin 3 |
|
RTN |
9 Way D-Type Pin 5 |
Panel Setup
Navigate to the RS232 Port.
Set type to 3rd Party Device.
Set Baud rate to 9600.
Note:
To comply to EN54 standards, the instructions in CSL DualCom Pro 2 Fire EN54 Variant Quick Guide must also be followed.
The non-isolated DB9 printer port should be used for connecting to the DualCom Pro.