Honeywell Gent – RS232
Panel Connection – RS232
|
Manufacturer |
Honeywell |
|
Model |
Gent |
|
Version |
Fire panel must be running the 3400 Basic Communications Protocol (issue 1.13 or later) |
|
Panel Profile |
HONEYWELL-GENT-RS232 |
|
Panel Connection |
RS232 |
|
Technical Notes |
There are 3 SIA reporting modes which provide different ways of reporting fire panel events and alarm information. The default mode 0 is recommended. If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
DualCom Pro to Panel Wiring
|
RS232-T |
Card 0 Port 1 RX1 |
|
RS232-R |
Card 0 Port 1 TX1 |
|
RTN |
Card 0 Port 1 0V |
Panel Setup
Alarms should be set up on the panel for RS232 Card 0 Port 1.
The port mode should be set as Universal, and the port speed (baud) should be set to 19200.
Note: If Card 0 Port 1 is being used for something else than use Card0 Port 2 instead and wire accordingly.