Panel Guide

Honeywell Notifier – RS232

Panel Connection – RS232

Manufacturer

Honeywell

Model

Notifier

Version

ID2000

Cable Required?

Unterminated serial cable with 9 Way D-Type IDC socket.

Panel Profile

NOTIFIER-PRINTER-RS232

Panel Connection

RS232

Technical Notes

ID3000 is not supported.

If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide.

Panel Connection Information

RS232-T

9 Way D-Type Pin 2

RS232-R

9 Way D-Type Pin 3

RTN

9 Way D-Type Pin 5

Panel Setup

Navigate to the RS232 Port.

Set type to 3rd Party Device.

Set Baud rate to 9600.

Note:

To comply to EN54 standards, the instructions in CSL DualCom Pro 2 Fire EN54 Variant Quick Guide must also be followed.

The non-isolated DB9 printer port should be used for connecting to the DualCom Pro.