Honeywell Notifier – RS232
Panel Connection – RS232
Manufacturer | Honeywell |
Model | Notifier |
Version | ID2000 |
Cable Required? | Unterminated serial cable with 9 Way D-Type IDC socket. |
Panel Profile | NOTIFIER-PRINTER-RS232 |
Panel Connection | RS232 |
Technical Notes | ID3000 is not supported. If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide. |
Panel Connection Information
RS232-T | 9 Way D-Type Pin 2 |
RS232-R | 9 Way D-Type Pin 3 |
RTN | 9 Way D-Type Pin 5 |
Panel Setup
Navigate to the RS232 Port.
Set type to 3rd Party Device.
Set Baud rate to 9600.
Note:
To comply to EN54 standards, the instructions in CSL DualCom Pro 2 Fire EN54 Variant Quick Guide must also be followed.
The non-isolated DB9 printer port should be used for connecting to the DualCom Pro.