Panel Guide

Honeywell Galaxy G3, Classic, Dimension – RS232

Panel Connection

Manufacturer

Honeywell

Model

Galaxy

Version

Dimension, G3, Classic

Minimum Panel Firmware

V1.4

Cable required?

Hardware from DualCom Pro to the Panel:

Pro 232 R to TX of panel

Pro 232 T to RX of panel

Pro RTN to Neg of panel

Panel Profile

HONEYWELL-GALAXY-RS232

Panel Connection

RS232

Panel Connection Information

Manufacturer

Panel

Connection

Cable/Plug On

Supplied Cables

Honeywell

Galaxy G3/Dimension

RS232 TX & RX

Normal Alarm Cable

RS232 T – RX
RS232 R – TX
RTN – GND (RS485)

Panel Programming

  • “Engineer Menu” 56 > Menu 6 – Int RS232 1
  • Select “Mode” – Direct > Select “Format SIA” > Enter “SIA” (option 2) > “SIA level 3”
  • Ensure “Trigger 10” is “On” > Ensure “Trigger 18” is “On” > “Activate” any further triggers which are
  • required
  • Enter “Account Number” <_____> (Chip ID) > Select “Comms Setup” > Enter “Baud Rate” 57600
  • Enter “Data Bits” – 8 > Enter “Stop Bits” – 1 > Select “Parity” – No Parity
  • Escape to return to “Engineer Mode”
  • Exit “Engineering Mode” into “Day Mode” Galaxy Troubleshooting

Troubleshooting

  • Menu 23: Panel Firmware Version
  • Menu 62: Full Set inside Engineering
  • Galaxy panels running version V1.4 and below cannot support SIA and are a pins only integration
  • Panel Manufacturer’s Default Codes – USER: 1234 or USER 1,2,3,4,5
  • Panel Manufacturer’s Default Codes – ENGINEER: 112233
  • Due to Panel Integration on RS232, Line Fault & Fail to Set are only available as SIA events on a
    RS485 integration
  • When using this connection method, alarms will not be delivered whilst carrying out UDL