In brief

Traditional analogue telephone lines carry a small electrical supply from the telephone exchange, allowing a basic corded telephone to work without mains power at the premises. Digital replacements do not provide that same line power, so communication depends on locally powered equipment such as a broadband router, telephone adapter, optical network termination point or mobile communicator. 

Telecare devices and building systems may have batteries that keep the main system operating, but these will not necessarily support every component in its communication path. Back-up arrangements must therefore keep all the necessary equipment powered, whether it draws power from the system itself or from a separate supply. Otherwise, the system may continue to operate while losing its route to the monitoring or receiving centre. 

Depending on the installation, the solution may involve powering the signalling unit from the system’s backed-up supply, providing battery back-up for broadband equipment, or selecting a radio path that avoids dependence on the premises’ router. The complete arrangement should then be tested to confirm that calls or alarm signals can still reach their destination during a mains failure. 

Replacement lines draw power from the building, not the exchange

Openreach will switch off the analogue public switched telephone network (PSTN) on 31 January 2027. Figures it released on 30 October 2026 showed about one million copper lines still active, 300,000 of them at business premises.

Openreach names these among the systems still relying on copper: 

  • payment devices and cash handling systems 
  • lift emergency telephones and auto-diallers 
  • fire alarm communication panels and security monitoring systems 
  • building access controls, automated gates and door entry units 
  • industrial telemetry and building energy management systems 

A traditional PSTN line draws its power from the local telephone exchange (Ofcom’s power-cut guidance), so the line itself stays live when the building loses mains power. The alarm panel or dialler on that line may depend on its own batteries or another back-up supply. A digital line over broadband, however, runs through a router that draws mains power in the building. A full-fibre connection also depends on an optical network termination point (ONT), the powered unit where the fibre terminates inside the premises. The ONT draws its power from a socket on the premises, in some installations through a battery back-up unit. 

Why broadband back-up matters

Recent research commissioned by Uswitch found that, among UK adults who had experienced broadband loss in the previous 12 months, 42 per cent cited a power cut, ahead of faults at their broadband provider at 31 per cent. Among those whose landline connects through a broadband router, almost a third were unaware that it stops working during a broadband outage or power cut. 

The research concerns household broadband rather than building systems or telecare specifically. However, the same underlying dependency applies: if a system communicates through broadband, the router and any other essential equipment supporting that connection must remain powered.

Emergency-call back-up is not the same as alarm-signalling resilience

Ofcom’s guidance of 10 October 2018 expects phone providers to have at least one solution available for a power cut at the customer’s premises. The solution should give access to the emergency services for at least one hour. It should be free to customers who are at risk because they depend on their landline. The solutions Ofcom describes include a battery back-up unit that powers the router, and a mobile handset. 

The guidance concerns calls to emergency organisations such as the police, fire and ambulance services. Alarm receiving centres, the 2018 guidance notes, were not classified as emergency organisations. Ofcom states that it “cannot compel providers” to ensure access to them during a power outage. How long a fire or security system keeps its path to a receiving centre depends on the equipment in that path. 

Keeping the complete communication path powered

For a system that communicates over broadband, suitable battery back-up or an uninterruptible power supply can keep the router and, on full-fibre connections, the ONT operating during a mains failure. Any other essential equipment along the route also needs to remain powered. The back-up capacity should be selected for the equipment being supported and the required operating period. 

A radio path provided by the system’s signalling unit does not pass through the premises’ broadband router or ONT, although the signalling unit still requires suitable power. A LAN path continues to depend on the locally powered equipment supporting the building’s broadband connection. Broadband, radio and combined path configurations can each support resilient communication when the necessary equipment has suitable back-up power. The appropriate choice depends on the installation, required operating period and level of path diversity. 

Dual-path signalling adds resilience by providing two monitored routes to the alarm receiving centre. Depending on the signalling configuration, these may use two radio connections or a combination of LAN and radio. Designing suitable back-up power for the complete signalling arrangement helps preserve the benefit of this path diversity during a mains failure. 

For each system still using an analogue service, review the equipment, power supplies and communication routes together: 

  • how long the system itself can operate during a power cut, and whether its communication paths can remain available for the same required period 
  • which equipment each path passes through between the system and the network 
  • what powers each piece of that equipment, and for how long 
  • how the power arrangements support both the primary and secondary communication paths 
  • whether the replacement connection has been tested under simulated mains-failure conditions, including confirmation that alarms or test signals still reach the receiving centre, with the system maintainer coordinating the test and any necessary receiving-centre arrangements 

Keeping fire, security and lift systems connected beyond the PSTN

CSL provides managed connectivity for critical IoT and safety applications. CSL’s alarm signalling products and services include single-path and dual-path configurations that deliver fire and security alarms and data from protected premises to alarm receiving centres. VoiceLink, which serves lift alarms and emergency lines, moves legacy analogue systems to 4G Voice over LTE (VoLTE). In a power cut, the VoiceLink unit’s built-in battery keeps it available for up to eight hours on standby, or two hours of talk time. 

For fire and security signalling, selecting an appropriate single-path or dual-path configuration can reduce dependence on legacy telephone services and provide resilient, monitored connectivity to the alarm receiving centre. For lift emergency lines, VoiceLink provides a dedicated 4G replacement with built-in battery back-up. Across these and other connected applications, the replacement connection, power arrangements and required operating period should be considered together and tested with the relevant monitoring or receiving centre. 

To discuss connectivity and power back-up for building systems and telecare ahead of the PSTN switch-off, contact sales@csl-group.com. 

Find out more: CSL PSTN switch-off resources 

Published on: 18th November, 2026
Sectors: Building & Security, Healthcare & Telecare, Infrastructure, Public Sector, Retail & Hospitality, Transport & Logistics, Utilities
Applications: Alarm Signalling, Security & Surveillance, Telecare/Remote Monitoring