Panel Guide
Honeywell Galaxy G3, Classic, Dimension – RS232
Panel Connection
|
Manufacturer |
Honeywell |
|
Model |
Galaxy |
|
Version |
Dimension, G3, Classic |
|
Minimum Panel Firmware |
V1.4 |
|
Cable required? |
Hardware from DualCom Pro to the Panel: Pro 232 R to TX of panel Pro 232 T to RX of panel Pro RTN to Neg of panel |
|
Panel Profile |
HONEYWELL-GALAXY-RS232 |
|
Panel Connection |
RS232 |
Panel Connection Information
|
Manufacturer |
Panel |
Connection |
Cable/Plug On |
Supplied Cables |
|
Honeywell |
Galaxy G3/Dimension |
RS232 TX & RX |
Normal Alarm Cable |
RS232 T – RX |
Panel Programming
- “Engineer Menu” 56 > Menu 6 – Int RS232 1
- Select “Mode” – Direct > Select “Format SIA” > Enter “SIA” (option 2) > “SIA level 3”
- Ensure “Trigger 10” is “On” > Ensure “Trigger 18” is “On” > “Activate” any further triggers which are
- required
- Enter “Account Number” <_____> (Chip ID) > Select “Comms Setup” > Enter “Baud Rate” 57600
- Enter “Data Bits” – 8 > Enter “Stop Bits” – 1 > Select “Parity” – No Parity
- Escape to return to “Engineer Mode”
- Exit “Engineering Mode” into “Day Mode” Galaxy Troubleshooting
Troubleshooting
- Menu 23: Panel Firmware Version
- Menu 62: Full Set inside Engineering
- Galaxy panels running version V1.4 and below cannot support SIA and are a pins only integration
- Panel Manufacturer’s Default Codes – USER: 1234 or USER 1,2,3,4,5
- Panel Manufacturer’s Default Codes – ENGINEER: 112233
- Due to Panel Integration on RS232, Line Fault & Fail to Set are only available as SIA events on a
RS485 integration - When using this connection method, alarms will not be delivered whilst carrying out UDL