Panel Connection – RS232

Manufacturer Carrier
Model Aritech 2X-F2-S Fire Panel with Panel Isolator Board 2010-2-232-IB
Version N/A
Cable required? Aritech 2010-2-232-C30
Panel Profile ARITECH-2XF2S-RS232
Panel Bus Connection RS232
Technical Notes

The panel isolator board must be plugged into the panel’s COM1 port.

If an EN54-compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide.

Panel Connection Information

Connection Panel
RS232-T Socket Pin 3
RS232-R Socket Pin 1
RTN Socket Pin 5

IMPORTANT - The panel isolator board must be plugged into the panel’s COM1 port.

    Panel Programming

    • Navigate to [Printer config] and press [Enter].
    • Navigate to [Ext printer config] and press [Enter].
    • Set baud rate for the Ext printer port to 19200.
    • Select [Used] and remove [tick]. This will deselect COM0 port and enable COM1 port.
    • Select which events to print