Panel Connection – RS232

Manufacturer Advanced
Model Hertek
Version Penta with Optional BMS Interface Module (MXP-510)
Minimum Panel Firmware BMS firmware V52019ar or greater
Cable required?

Direct wiring as shown below

Panel Profile PENTA-RS232
Panel Connection RS232
Technical Notes

The DualCom Pro can be wired to either the Panel onboard RS232 connector or the MXP-510 module RS232 when fitted.

If an EN54 compliant installation is required, please also follow the instructions in the DualCom Pro 2 Fire EN54 Variant Quick Guide

Panel Connection Information

RS232-T Panel’s RS232 RX MXP-510 RS232 RX
RS232-R Panel’s RS232 TX MXP-510 RS232 TX
RTN Panel’s RS232 GND MXP-510 RS232 GND