This website stores cookies on your computer. These cookies are used to improve our website and provide more personalised services to you, both on this website and through other media. To find out more about the cookies we use, and information on how to block or delete cookies, please see our Privacy Policy. If you continue to use this site, you are consenting to our use of cookies.

Choose Language:

DualCom Pro 2

Dimensions 90mm (h) x 142mm (w) x 22mm (d)
Weight 189g excluding aerial
Temperature -10 °C to + 55 °C
Humidity 0 - 90% non-condensing
Mounting

Via fixing points under main cover

Warranty 5 years
Power Requirement

10 - 36 Volts DC

In order to maintain compliance with requirements for electrical safety the Dualcom Pro should always be powered from a fused supply with following rating:

  • For a 12V DC system (supply voltage in the range 10 Volts DC to 14 Volts DC) a fuse rated at 1.25
  • For a 24V DC system (supply voltage in the range 20 Volts DC to 36 Volts DC) a fuse rated at 600 mA

If the power source is not limited to these values, then a fuse with the correct rating must be fitted in line with the positive connection from the power source.
The SPT will shut down on detecting a low supply of 7.6 Volts DC +/- 0.5 Volts DC

Current Consumption

DigiAir Pro 2 Radio 12V Power Supply: 103 mA (average value)

DigiAir Pro 2 Radio 24V Power Supply: 59 mA (average value)

DigiAir Pro 2 LAN 12V Power Supply: 96 mA (average value)

DigiAir Pro 2 LAN 24V Power Supply: 55 mA (average value)

GradeShift Pro 2 LAN Radio 12V Power Supply: 100 mA (average value)

GradeShift Pro 2 LAN Radio 24V Power Supply: 63 mA (average value)

GradeShift Pro 2 Dual Radio 12V Power Supply: 120 mA (average value)

GradeShift Pro 2 Dual Radio 24V Power Supply: 72 mA (average value)
Radio Path 2G, 3G, 4G
Output Ratings Maximum applied voltage = 60VMaximum current = 150mA
Aerial 50 ohms (nominal) on MMCX socket
Operation Method Store and forward
CIE Interconnections Input triggering (standardised parallel), RS232, RS485, TTL
RCT Protocols SIA
Input Terminals Max +30 Volts, Min 0 Volts DC (reference supply 0V) with a + or – 40% change for > 200ms.
Low Battery 7.6V DC +/- 0.5 VDC
User Serviceable Parts There are no serviceable parts within the DualCom Pro Range
Applicable Standards

Suitable for use in alarm systems complying to:

  • EN50131-1:2006+A2:2017
  • EN50136-1:2012+A1:2018
  • PD6662:2017
  • PD6669:2017

Emissions Standard – Radio Equipment Directive 2014/53/EU (RED)

EN 50130-5 Environmental Class II
ATS Classification EN 50136-2:2013 SP2, SP3, SP4, DP1, DP2, DP3, DP4

ATS Configuration EN 50131-10:2014 Type Y

ATS Classification EN 50136-1-1:1998

  • Radio D3, M3, T4, S2, I3, A4 (ATS5)
  • LAN D3, M3, T4, S2, I3, A4 (ATS5)